Battery Calculator
Fire Alarm Panel — AS7240.2
Calculate the required battery capacity for your fire alarm panel based on quiescent and alarm loads. Generate a branded report for your records.
Battery Calculation
Report Details
Required Capacity
—
Amp-hours (Ah)
Formula: 1.25 × ((Standby hrs × Quiescent) + (2 × (Alarm load × Alarm hrs)))
AS7240.2 — Battery Capacity Requirements
In the event of primary power failure, batteries must maintain the system in quiescent mode for the required standby period, then power two worst-case alarm zones for the required alarm duration. New batteries must provide at least 125% (L=1.25) of calculated capacity to account for 20% capacity loss over the battery's useful life. A capacity de-rating factor (FC) of 2 is applied to the alarm load to account for discharge rate characteristics.

Generated using the Essential Fire Services Battery Calculator
Fire Protection, Perfected.
All calculations should be verified by a qualified fire protection technician.